London Electrical Inspection & Testing
Tests Carried Out
Continuity of Protective Conductors and Equipotential Bonding conductors
If any electrical installation can be isolated from the supply it is permissible
to disconnect the protective and equipotential conductors from the main earthing
terminal in order to verify their continuity. The sequence of operation needed
for initial testing can be carried out safely on an existing installation if
it is isolated from the supply.
Where an electrical installation cannot be isolated from the supply, the protective
equipotential conductors must NOT be disconnected as, under fault conditions,
the exposed and extraneous-conductive-parts could be raised to a dangerous level
above earth potential. The 'combined' integrity of the conductors shall be established
by continuity/earth fault loop impedance tests. The former to establish continuity
of conductors and the latter to establish and confirm an appropriate disconnection
time in the event of an earth fault.
Polarity
Test shall be made to verify that:-
- the polarity is correct at the meter and consumer unit/distribution
board
- single-pole control and protective devices are connected in
the phase conductor only
- conductors are correctly connected to socket-outlets and other
accessories/equipment
- centre-contact bayonet and Edison-type screw lamp-holders have
their outer or screwed contacts connected to the earthed neutral conductor
- all multi-pole devices are correctly installed
Earth Fault Loop Impedance
Where protective measures are used which require a knowledge of earth fault
loop impedance, the relevant impedance shall be measured, or determined by an
equally effective method.
Earth fault loop impedance tests are carried out at the locations indicated
below:-
- at the origin of each installation and at each Distribution
Board
- fixed equipment and socket-outlets
- 10 per cent (on a random basis) of all luminaires, with a minimum
of one luminaire, preferably the further one from the consumer units, for each
circuit of any building
- at any location which may be exposed to exceptional damage
or deterioration or represent a special hazard at the furthest point of every
radial circuit
Where the installation incorporates an R.C.D., the value of earth fault loop
impedance obtained in the test should be related to the nominal residual operating
device.
Insulation Resistance
Insulation resistance tests should be made on a dead circuit and any electronic
equipment which might be damaged by application of the test voltage must be disconnected
or isolated. The insulation resistance should be measured between each live conductor
and earth and should not be less than 0.5 megohm. Where practicable the tests
are applied to the whole of the installation with all fuse links in place and
all switches closed. Alternatively, the installation may be tested in parts.
Operation of Devices for Isolation and Switching
Where means are provided in accordance with the requirements of the Regulations
for isolation and switching, a 10 per cent sample shall be operated to verify
their effectiveness and checked to ensure adequate and correct labeling.
Operation of Residual Current Devices (RCD’s)
Where protection is provided by an R.C.D., the effective operation of each
R.C.D. shall be verified by a test simulating an appropriate fault condition
independent of any test facility incorporated in the device, followed by operation
of the integral test device. The nominal rated tripping current for protection
of a socket-outlet for use with equipment outdoors or physically installed outside
the general installation equipotential zone must not exceed 30mA (0.03 amps).
In certain situations such as high risk areas, 10mA (0.01 amps) RCD may be
appropriate for the particular installation.
Operation of Over-Current Circuit-Breakers
Where protection against over current is provided by circuit-breakers, the
manual operating mechanism of each circuit breaker will be operated to verify
that the device opens and closes satisfactorily.
^ Top
|